 "format": "coredash.scenario/v1",
 "site": "DEMO-01",
 "description": "ช่วงพีคเช้า: ปั๊มตัวที่ 2 เดินเสริมตาม Interval แล้วหยุดเมื่อความต้องการลด",
 "loop": true,
 "interpolate": true,
 "settings": {
  "CTRL.sp": 4.0,
  "CTRL.kp": 0.8,
  "CTRL.ti": 3.0,
  "CTRL.deadband": 0.15,
  "CTRL.int_start": 30,
  "CTRL.int_stop": 60,
  "CTRL.alt_hours": 6,
  "CTRL.low_alarm": 3.5,
  "CTRL.high_alarm": 5.5
 },
 "frames": [
  {
   "t": 0,
   "values": {
    "system.pressure": 4.01,
    "FT-01.flow": 114.7,
    "FT-01.total": 128450.0,
    "PM-01.kw": 19.64,
    "PM-01.kwh": 86520.0,
    "PM-01.hz": 50.0,
    "PM-01.pf": 0.93,
    "MCC.phase": 1,
    "MCC.estop": 0,
    "MCC.cab_temp": 34.0,
    "CTRL.lead": 1,
    "CTRL.mode": 0,
    "PM-01.v_l1": 398.8,
    "PM-01.a_l1": 30.1,
    "PM-01.v_l2": 400.0,
    "PM-01.a_l2": 30.5,
    "PM-01.v_l3": 401.2,
    "PM-01.a_l3": 30.8,
    "P-01.freq": 45,
    "P-01.speed": 1332,
    "P-01.current": 36.4,
    "P-01.power": 18.34,
    "P-01.torque": 55.1,
    "P-01.dcbus": 539.1,
    "P-01.vout": 360,
    "P-01.pid_fb": 4.01,
    "P-01.pid_out": 90,
    "P-01.run": 1,
    "P-01.ready": 1,
    "P-01.fault": 0,
    "P-02.freq": 0,
    "P-02.speed": 0,
    "P-02.current": 0,
    "P-02.power": 0,
    "P-02.torque": 0,
    "P-02.dcbus": 540.0,
    "P-02.vout": 0,
    "P-02.pid_fb": 4.01,
    "P-02.pid_out": 0,
    "P-02.run": 0,
    "P-02.ready": 1,
    "P-02.fault": 0
   },
   "note": "ปกติ ปั๊มหลักตัวเดียว"
  },
  {
   "t": 30,
   "values": {
    "system.pressure": 3.98,
    "FT-01.flow": 171.8,
    "FT-01.total": 128450.3,
    "PM-01.kw": 28.28,
    "PM-01.kwh": 86520.1,
    "PM-01.hz": 50.0,
    "PM-01.pf": 0.93,
    "MCC.phase": 1,
    "MCC.estop": 0,
    "MCC.cab_temp": 34.4,
    "CTRL.lead": 1,
    "CTRL.mode": 0,
    "PM-01.v_l1": 398.8,
    "PM-01.a_l1": 43.4,
    "PM-01.v_l2": 400.0,
    "PM-01.a_l2": 43.9,
    "PM-01.v_l3": 401.2,
    "PM-01.a_l3": 44.4,
    "P-01.freq": 48,
    "P-01.speed": 1421,
    "P-01.current": 49.8,
    "P-01.power": 26.98,
    "P-01.torque": 76.0,
    "P-01.dcbus": 538.7,
    "P-01.vout": 384,
    "P-01.pid_fb": 3.98,
    "P-01.pid_out": 96,
    "P-01.run": 1,
    "P-01.ready": 1,
    "P-01.fault": 0,
    "P-02.freq": 0,
    "P-02.speed": 0,
    "P-02.current": 0,
    "P-02.power": 0,
    "P-02.torque": 0,
    "P-02.dcbus": 540.0,
    "P-02.vout": 0,
    "P-02.pid_fb": 3.98,
    "P-02.pid_out": 0,
    "P-02.run": 0,
    "P-02.ready": 1,
    "P-02.fault": 0
   }
  },
  {
   "t": 60,
   "values": {
    "system.pressure": 3.86,
    "FT-01.flow": 205.9,
    "FT-01.total": 128450.8,
    "PM-01.kw": 32.56,
    "PM-01.kwh": 86520.1,
    "PM-01.hz": 50.0,
    "PM-01.pf": 0.93,
    "MCC.phase": 1,
    "MCC.estop": 0,
    "MCC.cab_temp": 34.6,
    "CTRL.lead": 1,
    "CTRL.mode": 0,
    "PM-01.v_l1": 398.8,
    "PM-01.a_l1": 49.9,
    "PM-01.v_l2": 400.0,
    "PM-01.a_l2": 50.5,
    "PM-01.v_l3": 401.2,
    "PM-01.a_l3": 51.1,
    "P-01.freq": 49.8,
    "P-01.speed": 1474,
    "P-01.current": 56.4,
    "P-01.power": 31.26,
    "P-01.torque": 84.8,
    "P-01.dcbus": 538.4,
    "P-01.vout": 398,
    "P-01.pid_fb": 3.86,
    "P-01.pid_out": 99.6,
    "P-01.run": 1,
    "P-01.ready": 1,
    "P-01.fault": 0,
    "P-02.freq": 0,
    "P-02.speed": 0,
    "P-02.current": 0,
    "P-02.power": 0,
    "P-02.torque": 0,
    "P-02.dcbus": 540.0,
    "P-02.vout": 0,
    "P-02.pid_fb": 3.86,
    "P-02.pid_out": 0,
    "P-02.run": 0,
    "P-02.ready": 1,
    "P-02.fault": 0
   },
   "note": "ความต้องการน้ำเพิ่ม ปั๊มหลักเต็มรอบ"
  },
  {
   "t": 90,
   "values": {
    "system.pressure": 3.72,
    "FT-01.flow": 216.8,
    "FT-01.total": 128451.4,
    "PM-01.kw": 33.01,
    "PM-01.kwh": 86520.2,
    "PM-01.hz": 50.0,
    "PM-01.pf": 0.93,
    "MCC.phase": 1,
    "MCC.estop": 0,
    "MCC.cab_temp": 34.7,
    "CTRL.lead": 1,
    "CTRL.mode": 0,
    "PM-01.v_l1": 398.8,
    "PM-01.a_l1": 50.6,
    "PM-01.v_l2": 400.0,
    "PM-01.a_l2": 51.2,
    "PM-01.v_l3": 401.2,
    "PM-01.a_l3": 51.9,
    "P-01.freq": 50,
    "P-01.speed": 1480,
    "P-01.current": 57.2,
    "P-01.power": 31.71,
    "P-01.torque": 85.7,
    "P-01.dcbus": 538.4,
    "P-01.vout": 400,
    "P-01.pid_fb": 3.72,
    "P-01.pid_out": 100,
    "P-01.run": 1,
    "P-01.ready": 1,
    "P-01.fault": 0,
    "P-02.freq": 0,
    "P-02.speed": 0,
    "P-02.current": 0,
    "P-02.power": 0,
    "P-02.torque": 0,
    "P-02.dcbus": 540.0,
    "P-02.vout": 0,
    "P-02.pid_fb": 3.72,
    "P-02.pid_out": 0,
    "P-02.run": 0,
    "P-02.ready": 1,
    "P-02.fault": 0
   },
   "note": "แรงดันต่ำกว่า SP-Deadband ครบ 30 วินาที → สั่งปั๊มตัวที่ 2"
  },
  {
   "t": 100,
   "values": {
    "system.pressure": 3.8,
    "FT-01.flow": 184.5,
    "FT-01.total": 128452.0,
    "PM-01.kw": 29.54,
    "PM-01.kwh": 86520.3,
    "PM-01.hz": 50.0,
    "PM-01.pf": 0.93,
    "MCC.phase": 1,
    "MCC.estop": 0,
    "MCC.cab_temp": 34.5,
    "CTRL.lead": 1,
    "CTRL.mode": 0,
    "PM-01.v_l1": 398.8,
    "PM-01.a_l1": 45.3,
    "PM-01.v_l2": 400.0,
    "PM-01.a_l2": 45.8,
    "PM-01.v_l3": 401.2,
    "PM-01.a_l3": 46.4,
    "P-01.freq": 48,
    "P-01.speed": 1421,
    "P-01.current": 50.8,
    "P-01.power": 27.64,
    "P-01.torque": 77.8,
    "P-01.dcbus": 538.6,
    "P-01.vout": 384,
    "P-01.pid_fb": 3.8,
    "P-01.pid_out": 96,
    "P-01.run": 1,
    "P-01.ready": 1,
    "P-01.fault": 0,
    "P-02.freq": 30,
    "P-02.speed": 888,
    "P-02.current": 8.9,
    "P-02.power": 0.6,
    "P-02.torque": 2.7,
    "P-02.dcbus": 540.0,
    "P-02.vout": 240,
    "P-02.pid_fb": 3.8,
    "P-02.pid_out": 60,
    "P-02.run": 1,
    "P-02.ready": 1,
    "P-02.fault": 0
   }
  },
  {
   "t": 130,
   "values": {
    "system.pressure": 4.0,
    "FT-01.flow": 231.5,
    "FT-01.total": 128452.5,
    "PM-01.kw": 38.23,
    "PM-01.kwh": 86520.4,
    "PM-01.hz": 50.0,
    "PM-01.pf": 0.93,
    "MCC.phase": 1,
    "MCC.estop": 0,
    "MCC.cab_temp": 34.9,
    "CTRL.lead": 1,
    "CTRL.mode": 0,
    "PM-01.v_l1": 398.8,
    "PM-01.a_l1": 58.6,
    "PM-01.v_l2": 400.0,
    "PM-01.a_l2": 59.3,
    "PM-01.v_l3": 401.2,
    "PM-01.a_l3": 60.0,
    "P-01.freq": 45,
    "P-01.speed": 1332,
    "P-01.current": 36.6,
    "P-01.power": 18.46,
    "P-01.torque": 55.4,
    "P-01.dcbus": 539.1,
    "P-01.vout": 360,
    "P-01.pid_fb": 4.0,
    "P-01.pid_out": 90,
    "P-01.run": 1,
    "P-01.ready": 1,
    "P-01.fault": 0,
    "P-02.freq": 45,
    "P-02.speed": 1332,
    "P-02.current": 36.6,
    "P-02.power": 18.46,
    "P-02.torque": 55.4,
    "P-02.dcbus": 539.1,
    "P-02.vout": 360,
    "P-02.pid_fb": 4.0,
    "P-02.pid_out": 90,
    "P-02.run": 1,
    "P-02.ready": 1,
    "P-02.fault": 0
   },
   "note": "ปั๊ม 2 ตัวรักษา 4.0 bar (~230 m³/h)"
  },
  {
   "t": 250,
   "values": {
    "system.pressure": 4.01,
    "FT-01.flow": 229.3,
    "FT-01.total": 128453.1,
    "PM-01.kw": 37.98,
    "PM-01.kwh": 86520.5,
    "PM-01.hz": 50.0,
    "PM-01.pf": 0.93,
    "MCC.phase": 1,
    "MCC.estop": 0,
    "MCC.cab_temp": 34.9,
    "CTRL.lead": 1,
    "CTRL.mode": 0,
    "PM-01.v_l1": 398.8,
    "PM-01.a_l1": 58.2,
    "PM-01.v_l2": 400.0,
    "PM-01.a_l2": 58.9,
    "PM-01.v_l3": 401.2,
    "PM-01.a_l3": 59.7,
    "P-01.freq": 45,
    "P-01.speed": 1332,
    "P-01.current": 36.4,
    "P-01.power": 18.34,
    "P-01.torque": 55.1,
    "P-01.dcbus": 539.1,
    "P-01.vout": 360,
    "P-01.pid_fb": 4.01,
    "P-01.pid_out": 90,
    "P-01.run": 1,
    "P-01.ready": 1,
    "P-01.fault": 0,
    "P-02.freq": 45,
    "P-02.speed": 1332,
    "P-02.current": 36.4,
    "P-02.power": 18.34,
    "P-02.torque": 55.1,
    "P-02.dcbus": 539.1,
    "P-02.vout": 360,
    "P-02.pid_fb": 4.01,
    "P-02.pid_out": 90,
    "P-02.run": 1,
    "P-02.ready": 1,
    "P-02.fault": 0
   }
  },
  {
   "t": 280,
   "values": {
    "system.pressure": 4.02,
    "FT-01.flow": 177.9,
    "FT-01.total": 128453.8,
    "PM-01.kw": 30.1,
    "PM-01.kwh": 86520.6,
    "PM-01.hz": 50.0,
    "PM-01.pf": 0.93,
    "MCC.phase": 1,
    "MCC.estop": 0,
    "MCC.cab_temp": 34.5,
    "CTRL.lead": 1,
    "CTRL.mode": 0,
    "PM-01.v_l1": 398.8,
    "PM-01.a_l1": 46.2,
    "PM-01.v_l2": 400.0,
    "PM-01.a_l2": 46.7,
    "PM-01.v_l3": 401.2,
    "PM-01.a_l3": 47.3,
    "P-01.freq": 44,
    "P-01.speed": 1302,
    "P-01.current": 30.3,
    "P-01.power": 14.4,
    "P-01.torque": 44.2,
    "P-01.dcbus": 539.3,
    "P-01.vout": 352,
    "P-01.pid_fb": 4.02,
    "P-01.pid_out": 88,
    "P-01.run": 1,
    "P-01.ready": 1,
    "P-01.fault": 0,
    "P-02.freq": 44,
    "P-02.speed": 1302,
    "P-02.current": 30.3,
    "P-02.power": 14.4,
    "P-02.torque": 44.2,
    "P-02.dcbus": 539.3,
    "P-02.vout": 352,
    "P-02.pid_fb": 4.02,
    "P-02.pid_out": 88,
    "P-02.run": 1,
    "P-02.ready": 1,
    "P-02.fault": 0
   },
   "note": "ความต้องการลดลง"
  },
  {
   "t": 340,
   "values": {
    "system.pressure": 4.01,
    "FT-01.flow": 144.6,
    "FT-01.total": 128454.3,
    "PM-01.kw": 24.88,
    "PM-01.kwh": 86520.7,
    "PM-01.hz": 50.0,
    "PM-01.pf": 0.93,
    "MCC.phase": 1,
    "MCC.estop": 0,
    "MCC.cab_temp": 34.2,
    "CTRL.lead": 1,
    "CTRL.mode": 0,
    "PM-01.v_l1": 398.8,
    "PM-01.a_l1": 38.1,
    "PM-01.v_l2": 400.0,
    "PM-01.a_l2": 38.6,
    "PM-01.v_l3": 401.2,
    "PM-01.a_l3": 39.1,
    "P-01.freq": 43.4,
    "P-01.speed": 1285,
    "P-01.current": 26.3,
    "P-01.power": 11.79,
    "P-01.torque": 36.7,
    "P-01.dcbus": 539.4,
    "P-01.vout": 347,
    "P-01.pid_fb": 4.01,
    "P-01.pid_out": 86.8,
    "P-01.run": 1,
    "P-01.ready": 1,
    "P-01.fault": 0,
    "P-02.freq": 43.4,
    "P-02.speed": 1285,
    "P-02.current": 26.3,
    "P-02.power": 11.79,
    "P-02.torque": 36.7,
    "P-02.dcbus": 539.4,
    "P-02.vout": 347,
    "P-02.pid_fb": 4.01,
    "P-02.pid_out": 86.8,
    "P-02.run": 1,
    "P-02.ready": 1,
    "P-02.fault": 0
   },
   "note": "ถึงค่าตั้งครบ 60 วินาที → ปิดปั๊มตัวที่ 2"
  },
  {
   "t": 350,
   "values": {
    "system.pressure": 3.98,
    "FT-01.flow": 137.8,
    "FT-01.total": 128454.7,
    "PM-01.kw": 23.06,
    "PM-01.kwh": 86520.8,
    "PM-01.hz": 50.0,
    "PM-01.pf": 0.93,
    "MCC.phase": 1,
    "MCC.estop": 0,
    "MCC.cab_temp": 34.2,
    "CTRL.lead": 1,
    "CTRL.mode": 0,
    "PM-01.v_l1": 398.8,
    "PM-01.a_l1": 35.4,
    "PM-01.v_l2": 400.0,
    "PM-01.a_l2": 35.8,
    "PM-01.v_l3": 401.2,
    "PM-01.a_l3": 36.2,
    "P-01.freq": 46,
    "P-01.speed": 1362,
    "P-01.current": 41.7,
    "P-01.power": 21.76,
    "P-01.torque": 63.9,
    "P-01.dcbus": 538.9,
    "P-01.vout": 368,
    "P-01.pid_fb": 3.98,
    "P-01.pid_out": 92,
    "P-01.run": 1,
    "P-01.ready": 1,
    "P-01.fault": 0,
    "P-02.freq": 0,
    "P-02.speed": 0,
    "P-02.current": 0,
    "P-02.power": 0,
    "P-02.torque": 0,
    "P-02.dcbus": 540.0,
    "P-02.vout": 0,
    "P-02.pid_fb": 3.98,
    "P-02.pid_out": 0,
    "P-02.run": 0,
    "P-02.ready": 1,
    "P-02.fault": 0
   }
  },
  {
   "t": 420,
   "values": {
    "system.pressure": 4.01,
    "FT-01.flow": 114.7,
    "FT-01.total": 128455.0,
    "PM-01.kw": 19.64,
    "PM-01.kwh": 86520.8,
    "PM-01.hz": 50.0,
    "PM-01.pf": 0.93,
    "MCC.phase": 1,
    "MCC.estop": 0,
    "MCC.cab_temp": 34.0,
    "CTRL.lead": 1,
    "CTRL.mode": 0,
    "PM-01.v_l1": 398.8,
    "PM-01.a_l1": 30.1,
    "PM-01.v_l2": 400.0,
    "PM-01.a_l2": 30.5,
    "PM-01.v_l3": 401.2,
    "PM-01.a_l3": 30.8,
    "P-01.freq": 45,
    "P-01.speed": 1332,
    "P-01.current": 36.4,
    "P-01.power": 18.34,
    "P-01.torque": 55.1,
    "P-01.dcbus": 539.1,
    "P-01.vout": 360,
    "P-01.pid_fb": 4.01,
    "P-01.pid_out": 90,
    "P-01.run": 1,
    "P-01.ready": 1,
    "P-01.fault": 0,
    "P-02.freq": 0,
    "P-02.speed": 0,
    "P-02.current": 0,
    "P-02.power": 0,
    "P-02.torque": 0,
    "P-02.dcbus": 540.0,
    "P-02.vout": 0,
    "P-02.pid_fb": 4.01,
    "P-02.pid_out": 0,
    "P-02.run": 0,
    "P-02.ready": 1,
    "P-02.fault": 0
   }
  }
 ]
}